| AC Type |
Error Code |
Code Explanation |
| Daikin |
A1 |
Malfunction of indoor unit PCB Malfunction due to noise Defect of indoor unit PCB. |
| Malfunction of indoor unit PCB due to noise, defect of indoor unit PCB. |
| A3 |
Malfunction of drain level control system Drain piping clogging, improper drain piping work Defect of drain pump. Defect of float switch. |
| Malfunction of drain level control system, drain piping clogging, improper drain piping work, defect of drain pump. Defect of float switch. |
| A4 |
Malfunction of freezing protection Shortage of water volume Low water temperature setting Defect of 26WL. Defect of water temperature thermistor. |
| Malfunction of freeze protection, insufficient water volume, low water temperature setting, 26WL defect. Defect of water temperature thermistor. |
| A5 |
High pressure control in heating, freeze-up protection control in cooling Clogged air filter of indoor unit and short-circuit Defect of indoor unit heat exchanger thermistor. |
| High pressure control in heating, freeze-up protection control in cooling. Clogged indoor unit air filter and short circuit. Defect of indoor unit heat exchanger thermistor. |
| A6 |
Fan motor locked, overload, overcurrent Defect of connector contact Defect of indoor unit PCB Defect of fan motor. |
| Fan motor locked, overload, overcurrent. Defect of connector contact. Defect of indoor unit PCB. Defect of fan motor. |
| A7 |
Malfunction of swing flap motor Failure of swing flap motorm, Defect of indoor unit PCB Jammed swing mechanism/blade. |
| Malfunction of swing flap motor. Failure of swing flap motor, defect of indoor unit PCB, jammed swing mechanism/blade. |
| A8 |
Malfunction of power supply Overcurrent of AC input, Defect of power supply voltage. |
| Malfunction of power supply. Overcurrent of AC input, defect of power supply voltage. |
| A9 |
Malfunction of electronic expansion valve drive Defect of electronic expansion valve coil, Defect of indoor unit PCB, Defect of connector contact. |
| Malfunction of electronic expansion valve drive. Defect of electronic expansion valve coil, defect of indoor unit PCB, defect of connector contact. |
| AA |
Heater overheat 26WH is activated. |
| Heater overheat 26WH is activated. |
| AF |
Malfunction of a humidifier system Water leakage of humidifier (option), Failure of swing float switch. Improper drain piping incline. |
| Malfunction of humidifier system. Water leakage from humidifier (optional), failure of swing float switch. Improper drain piping incline. |
| AH |
Malfunction of dust collector of air cleaner Defect of dust collecting element Defect of high voltage power supply unit Stained insulator part Defect of indoor unit PCB. |
| Malfunction of air cleaner dust collector. Defect of dust collecting element. Defect of high voltage power supply unit. Stained insulator part. Defect of indoor unit PCB. |
| AJ |
Malfunction of capacity setting (Indoor unit PCB) Capacity setting adaptor is not installed when replacing PCB Defect of indoor unit PCB. |
| Malfunction of capacity setting (Indoor unit PCB). Capacity setting adapter not installed when replacing PCB. Defect of indoor unit PCB. |
| C1 |
Failure of transmission (between indoor unit PCB and fan PCB) Defect of transmission of fan motor control driver.
|
| Failure of transmission (between indoor unit PCB and fan PCB). Defect of transmission of fan motor control driver. |
| C4 |
Malfunction of liquid pipe thermistor for heat exchanger Defect of connector contact. Defect of liquid pipe thermistor for heat exchanger. |
| Malfunction of liquid pipe thermistor for heat exchanger. Defect of connector contact. Defect of liquid pipe thermistor for heat exchanger. |
| C5 |
Malfunction of gas pipe thermistor for heat exchanger Defect of connector contact. Defect of gas pipe thermistor for heat exchanger. |
| Malfunction of gas pipe thermistor for heat exchanger. Defect of connector contact. Defect of gas pipe thermistor for heat exchanger. |
| C6 |
Malfunction of fan motor control driver Defect of fan motor sensor system Defect of fan motor control driver. |
| Malfunction of fan motor control driver. Defect of fan motor sensor system. Defect of fan motor control driver. |
| C7 |
Front panel driving motor fault Defect of front panel driving motor Defect of limit switch. |
| Front panel driving motor fault. Defect of front panel driving motor. Defect of limit switch. |
| C9 |
Malfunction of suction air thermistor Defect of connector contact Defect of thermistor for suction air. |
| Malfunction of suction air thermistor. Defect of connector contact. Defect of thermistor for suction air. |
| CA |
Malfunction of discharge air thermistor Defect of connector contact. Defect of thermistor for discharge air. |
| Malfunction of discharge air thermistor. Defect of connector contact. Defect of thermistor for discharge air. |
| CC |
Malfunction of humidity sensor system Defect of connector contact Defect of humidity sensor. |
| Malfunction of humidity sensor system. Defect of connector contact. Defect of humidity sensor. |
| Midea |
E0 |
EEPROM parameter error |
| EEPROM parameter error |
| E1 |
Indoor / outdoor units communication protection |
| Indoor/outdoor units communication protection |
| E2 |
Zero-crossing signal error |
| Zero-crossing signal error |
| E3 |
Fan speed out of control |
| Fan speed out of control |
| E5 |
Open or short circuit of outdoor temperature sensor |
| Open or short circuit of outdoor temperature sensor |
| E6 |
Open or short circuit of room or evaporator temperature sensor |
| Open or short circuit of room or evaporator temperature sensor |
| P0 |
IGBT over-strong current protection |
| IGBT over-strong current protection |
| P1 |
Over voltage or too under voltage protection |
| Overvoltage or undervoltage protection |
| P2 |
Temperature protection of compressor top. |
| Compressor top temperature protection. |
| P4 |
Inverter compressor drive error |
| Inverter compressor drive error |
| YORK |
E0 |
Indoor EEPROM (Electrically Erasable Programmable Read-Only Memory) error |
| Indoor EEPROM (Electrically Erasable Programmable Read-Only Memory) error |
| E1 |
Indoor and outdoor unit communication malfunction |
| Indoor and outdoor unit communication malfunction |
| E3 |
Indoor fan speed malfunction |
| Indoor fan speed malfunction |
| E4 |
Indoor room temperature sensor error |
| Indoor room temperature sensor error |
| E5 |
Evaporator coil temperature sensor error |
| Evaporator coil temperature sensor error |
| EC |
Refrigerant leak detection system malfunction |
| Refrigerant leak detection system malfunction |
| EE |
Water level alarm malfunction |
| Water level alarm malfunction |
| E8 |
Dual indoor unit (twin model only) communication malfunction |
| Dual indoor unit (twin model only) communication malfunction |
| E9 |
Other twin model malfunction |
| Another twin model fault |
| E0 |
Overload protection |
| Overload protection |
| F1 |
Outdoor temperature sensor error |
| Outdoor temperature sensor error |
| F2 |
Outdoor condenser pipe sensor error |
| Outdoor condenser pipe sensor error |
| F3 |
Discharge air temperature sensor error
|
| Discharge air temperature sensor error |
| F4 |
Outdoor EEPROM (Electrically Erasable Programmable Read-Only Memory) error |
| Outdoor EEPROM (Electrically Erasable Programmable Read-Only Memory) error |
| F5 |
Outdoor fan speed (DC fan motor only) malfunction |
| Outdoor fan speed (DC fan motor only) malfunction |
| F6 |
T2b sensor error |
| T2b sensor error |
| F7 |
Auto-lifting panel communication error |
| Auto-lifting panel communication error |
| F8 |
Auto-lifting panel malfunction |
| Auto-lifting panel malfunction |
| F9 |
Auto-lifting panel is open |
| Auto-lifting panel is open |
| P0 |
Inverter module IPM protection |
| Inverter module IPM protection |
| P1 |
High/Low voltage protection |
| High/low voltage protection |
| P2 |
Compressor top overheating protection |
| Compressor top overheating protection |
| P3 |
Outdoor low temperature protection |
| Outdoor low temperature protection |
| P4 |
Compressor drive error |
| Compressor drive error |
| P5 |
Mode conflict |
| Mode conflict |
| P6 |
Compressor low-pressure protection |
| Compressor low-pressure protection |
| P7 |
Outdoor IGBT sensor error |
| Outdoor IGBT sensor error |
| AUX |
E1 |
Plastic temp sensor is abnormal.
|
| Plastic temp sensor is abnormal. |
| E2 |
Copper temp sensor is abnormal (outdoor) |
| Copper temp sensor is abnormal (outdoor) |
| E3 |
Copper temp sensor is abnormal (indoor) |
| Copper temp sensor is abnormal (indoor) |
| E4 |
PG motor feedback is abnormal |
| PG motor feedback is abnormal |
| E5 |
Abnormality of outdoor unit |
| Abnormality of outdoor unit |
| E6 |
Over-current oprotection |
| Over-current protection |
| E7 |
External feedback failure |
| External feedback failure |
| E8 |
Overheat protection |
| Overheat protection |
| E9 |
Water pump failure |
| Water pump failure |
| dF |
Indicates "dF"or defrosting indicator displays |
| Indicates "dF" or defrosting indicator displays |
| L1 |
Failure of coiled pipe sensor |
| Coiled pipe sensor failure |
| L2 |
Failure of room temperature sensor |
| Room temperature sensor failure |
| L6 |
Without feedback of internal fan motor |
| No feedback from internal fan motor |
| BEKO |
H1 |
Means defrosting status. It's the normal phenomenon. |
| Means defrosting status. It's a normal phenomenon. |
| E5 |
It can be eliminated after restarting the unit. If not, please contact qualified professionals for service. |
| It can be eliminated after restarting the unit. If not, please contact qualified professionals for service. |
| U8 |
It can be eliminated after restarting the unit. If not, please contact qualified professionals for service. |
| It can be eliminated after restarting the unit. If not, please contact qualified professionals for service. |
| H6 |
It can be eliminated after restarting the unit. If not, please contact qualified professionals for service. |
| It can be eliminated after restarting the unit. If not, please contact qualified professionals for service. |
| C5 |
Please contact qualified professionals for service. |
| Please contact qualified professionals for service. |
| F1 |
Please contact qualified professionals for service. |
| Please contact qualified professionals for service. |
| F2 |
Please contact qualified professionals for service. |
| Please contact qualified professionals for service. |
| Carrier |
E0 |
Indoor unit EEPROM parameter error |
| Indoor unit EEPROM parameter error |
| E1 |
Indoor / outdoor units communication error |
| Indoor/outdoor units communication error |
| E3 |
Indoor fan speed has been out of control |
| Indoor fan speed has been out of control |
| E4 |
Indoor room temperature sensor T1 open circuit or shortcircuit |
| Indoor room temperature sensor T1 open circuit or short circuit |
| E5 |
Evaporator coil temperature sensor T2 open circuit or short circuit |
| Evaporator coil temperature sensor T2 open circuit or short circuit |
| EC |
Refrigerant Leakage Detection |
| Refrigerant Leakage Detection |
| F1 |
Outdoor ambient temperature sensor T4 open circuit or short circuit |
| Outdoor ambient temperature sensor T4 open circuit or short circuit |
| F2 |
Condenser coil temperature sensor T3 open circuit or short circuit |
| Condenser coil temperature sensor T3 open circuit or short circuit |
| F3 |
Compressor discharge temperature sensor T5 open circuit or short circuit |
| Compressor discharge temperature sensor T5 open circuit or short circuit |
| F4 |
Outdoor unit EEPROM parameter error |
| Outdoor unit EEPROM parameter error |
| F5 |
Outdoor fan speed has been out of control |
| Outdoor fan speed is out of control |
| P0 |
IPM malfunction or IGBT over-strong current protection |
| IPM malfunction or IGBT over-current protection |
| P1 |
Over voltage or over low voltage protection |
| Overvoltage or undervoltage protection |
| P2 |
High temperature protection of compressor top diagnosis and solution |
| High temperature protection of compressor top diagnosis and solution |
| P4 |
Inverter compressor drive error |
| Inverter compressor drive error |
| P5 |
Mode conflict |
| Mode conflict |
| P6 |
Compressor voltage protection |
| |
Compressor voltage protection |
| Chigo |
E1 |
Condenser temperature sensor fault |
| Condenser temperature sensor fault |
| E2 |
Room temp. sensor fault |
| Room temperature sensor fault |
| E3 |
Coil temp. sensor fault |
| Coil temperature sensor fault |
| E4 |
Outdoor unit abnormal |
| Outdoor unit abnormal |
| E5 |
No feedback signal of indoor fan |
| No feedback signal from indoor fan |
| E6 |
No over zero signal |
| No over zero signal |
| E7 |
Outdoor feedback fault |
| Outdoor feedback fault |
| E8 |
Frost protection/over heat protection |
| Frost protection/overheat protection |
| F1 |
Communication fault |
| Communication fault |
| F2 |
Ambient temp. sensor fault |
| Ambient temperature sensor fault |
| F3 |
Coil pipe temp. sensor of indoor unit fault |
| Indoor unit coil pipe temperature sensor fault |
| F4 |
Fan motor of indoor |
| Indoor fan motor |
| F5 |
Module of outdoor unit fault |
| Outdoor unit module fault |
| F6 |
Ambient temp. sensor of outdoor fault |
| Outdoor ambient temperature sensor fault |
| F7 |
Coil pipe temp. sensor of outdoor unit fault |
| Outdoor unit coil pipe temperature sensor fault |
| F8 |
Suction temp. sensor of compressor fault |
| Compressor suction temperature sensor fault |
| F9 |
Discharge temp. sensor of compressor fault |
| Compressor discharge temperature sensor fault |
| FA |
Inductor of current or voltage fault |
| Current or voltage inductor fault |
| FC |
Compressor drive fault |
| Compressor drive fault |
| FD |
Phase lacking or phase sequence fault |
| Phase loss or phase sequence fault |
| FE |
Gas return sensor fault |
| Gas return sensor fault |
| FF |
Other fault |
| Other fault |
| P1 |
Temp. of evaporator protection |
| Evaporator temperature protection |
| P2 |
Overheat, over current protection of inverter module |
| Overheat, overcurrent protection of inverter module |
| P3 |
Over current protection |
| Overcurrent protection |
| P4 |
Discharge temp. of compressor protection |
| Compressor discharge temperature protection |
| P5 |
Over heat of compressor top protection |
| Overheat protection of compressor top |
| P6 |
Suction temp. of compressor protection |
| Compressor suction temperature protection |
| P7 |
Low or high voltage protection |
| Low or high voltage protection |
| P8 |
Low pressure of gas return protection |
| Low pressure of gas return protection |
| P9 |
High pressure of discharge protection |
| High pressure of discharge protection |
| PA |
High temp. of condenser protection |
| High temperature of condenser protection |
| PC |
High temp. of outdoor ambient protection |
| High temperature of outdoor ambient protection |
| PF |
Other protection |
| Other protection |
| DF |
Defrost indication |
| |
Defrost indication |
| Delonghi |
LE |
Low Temperature (frost prevention). The appliance is fitted with a frost protection device to avoid excessive formation of ice. The appliance starts up again automatically when the defrosting process is completed. |
| Low Temperature (frost prevention). The appliance is fitted with a frost protection device to avoid excessive formation of ice. The appliance starts up again automatically when the defrosting process is completed. |
| HL |
High Level (internal tray full). Empty the internal safety tray following the instructions in the section “End of season operations”. If it reoccurs in cooling mode, contact your local authorised customer services. In heating mode: empty the internal tray. |
| High level (internal safety tray is full). Empty the internal safety tray by following the instructions in the “End of Season Operations” section. If this recurs in cooling mode, contact local authorised customer services. In heating mode: Empty the internal tray. |
| CF |
Change filter. When this message is displayed, the water filter needs replacing as described in the section: “Replacing the limescale filter”. |
| Change filter. When this message is displayed, the water filter needs replacing as described in the section: “Replacing the limescale filter”. |
| PF |
Probe Failure (sensor damaged). If this is displayed, contact your local authorised service centre. |
| Probe Failure (sensor damaged). If this is displayed, contact your local authorised service centre. |
| F1 |
Failure 1. This message could appear if the water filter is particularly clogged. See section: “Replacing the limescale filter”. If the filter has been replaced recently, contact your local authorised service centre. |
| Failure 1. This message could appear if the water filter is particularly clogged. See section: “Replacing the limescale filter”. If the filter has been replaced recently, contact your local authorised service centre. |
| Lo |
Low Temperature - Room temperature is too low. |
| Low Temperature - Room temperature is too low. |
| H1 |
High Temperature - Room temperature is too high. |
| High Temperature - Room temperature is too high. |
| E1 |
Probe Failure ( Sensor Damaged). |
| Probe Failure (Sensor Damaged). |
| Fujitsu |
E0:00 |
Coms error - indoor to remote |
| Coms error - indoor to remote |
| E1:00 |
Coms error - indoor to outdoor |
| Coms error - indoor to outdoor |
| E2:00 |
Return air thermistor open circuit |
| Return air thermistor open circuit |
| E3:00 |
Return air thermistor short circuit |
| Return air thermistor short circuit |
| E4:00 |
Indoor coil thermistor open |
| Indoor coil thermistor open |
| E5:00 |
Indoor coil thermistor shorted |
| Indoor coil thermistor shorted |
| E6:00 |
Outdoor coil thermistor open |
| Outdoor coil thermistor open |
| E7:00 |
Outdoor coil thermistor shorted |
| Outdoor coil thermistor shorted |
| EA:00 |
Outdoor ambient thermistor open |
| Outdoor ambient thermistor open |
| Eb:00 |
Outdoor ambient thermistor shorted |
| Outdoor ambient thermistor shorted |
| Ec:00 |
Discharge pipe themistor open |
| Discharge pipe thermistor open |
| Ed:00 |
Discharge pipe thermistor shorted |
| Discharge pipe thermistor shorted |
| EE:00 |
High Pressure problem |
| High Pressure problem |
| EF:00 |
Discharge pipe temp. Problem - too high = short of gas |
| Discharge pipe temp. Problem - too high = short of gas |
| OO |
ID to RC Comms Fail |
| ID to RC Comms Fail |
| O1 |
ID to OD Comms Fail |
| ID to OD Comms Fail |
| O2 |
ID Air Sensor Open |
| ID Air Sensor Open |
| O3 |
ID Air Sensor Close |
| ID Air Sensor Close |
| O4 |
ID Pipe Sensor Open |
| ID Pipe Sensor Open |
| O5 |
ID Pipe Sensor Close |
| ID Pipe Sensor Close |
| O6 |
OD Pipe Sensor Fail |
| OD Pipe Sensor Fail |
| O8 |
Power Source Connection Failure |
| Power Source Connection Failure |
| O9 |
Drain Problem Float switch operated |
| Drain Problem Float switch operated |
| OA |
OD Air Sensor Fail |
| OD Air Sensor Fail |
| OC |
Discharge sensor Fail |
| Discharge sensor Fail |
| OE |
Outdoor High Pressure Heatsink error |
| Outdoor High Pressure Heatsink error |
| 11 |
OD PCB Fail |
| OD PCB Fail |
| 12 |
ID Fan Fail |
| ID Fan Fail |
| 13 |
OD Signal Abnormal ID signal error |
| OD Signal Abnormal ID signal error |
| 14 |
OD EEPROM Fail |
| OD EEPROM Fail |
| 15 |
Compressor Temp Failure |
| Compressor Temp Failure |
| 16 |
Pressure Switch Error |
| Pressure Switch Error |
| 17 |
IPM Error |
| IPM Error |
| 18 |
CT Error |
| CT Error |
| 19 |
Active Filter Module Error |
| Active Filter Module Error |
| 1A |
Compressor Failure |
| Compressor Failure |
| 1B |
OD Fan Failure |
| OD Fan Failure |
| 1C |
Inverter to PCB Comms Fail |
| Inverter to PCB Comms Fail |
| 1D |
2 Way Valve sensor Fail |
| 2 Way Valve sensor Fail |
| 1E |
Expansion Valve Error |
| Expansion Valve Error |
| 1F |
Connection ID Unit Error |
| Connection ID Unit Error |
| 20 |
Indoor manual switch abnormal |
| Internal manual switch abnormal |
| 24 |
Excessive high pressure protection on cooling |
| Excessive high pressure protection on cooling |
| 25 |
PFC circuit error |
| PFC circuit error |
| 26 |
Indoor signal error |
| Indoor signal error |
| 27 |
Indoor signal error |
| Indoor signal error |
| 28 |
Indoor heat exchanger temperature error |
| Indoor heat exchanger temperature error |
| 29 |
Outdoor heat exchanger temperature (middle) error |
| Outdoor heat exchanger temperature (middle) error |
| 2A |
Power supply frequency detection error |
| Power supply frequency detection error |
| 2B |
Compressor temperature error |
| Compressor temperature error |
| 2C |
Four-way valve abnormal |
| |
Four-way valve abnormal |
| General |
01 |
Indoor unit doesn’t accept signal from outdoor unit |
| Indoor unit does not accept signal from outdoor unit |
| 02 |
Room temperature sensor open |
| Room temperature sensor open |
| 03 |
Room temperature sensor short-circuited |
| Room temperature sensor short-circuited |
| 04 |
Indoor heat exchanger temperature sensor open |
| Indoor heat exchanger temperature sensor open |
| 05 |
Indoor heat exchanger temperature sensor short circuited |
| Indoor heat exchanger temperature sensor short-circuited |
| 06 |
Outdoor heat exchanger temperature sensor |
| Outdoor heat exchanger temperature sensor |
| 08 |
Power source connection error |
| Power source connection error |
| 09 |
Float switch operated |
| Float switch operated |
| 0A |
Outdoor temperature sensor error |
| Outdoor temperature sensor error |
| 0c |
Discharge pipe temperature sensor |
| Discharge pipe temperature sensor |
| 11 |
Model abnormal/Indoor EPROM Abnormal |
| Model abnormal / Indoor EPROM abnormal |
| 12 |
Indoor fan abnormal |
| Indoor fan abnormal |
| 13 |
Outdoor unit doesn’t accept the signal from indoor unit |
| Outdoor unit does not accept the signal from indoor unit |
| 14 |
Excessive outdoor pressure (permanent stop) |
| Excessive outdoor pressure (permanent stop) |
| 15 |
Compressor temperature sensor |
| Compressor temperature sensor |
| 16 |
Pressure switch error |
| Pressure switch error |
| 17 |
IPM error |
| IPM error |
| 18 |
CT error |
| CT error |
| 19 |
Active filter module (AFM) error |
| Active filter module (AFM) error |
| 1A |
Compressor does not operate |
| Compressor does not operate |
| 1b |
Outdoor unit fan error |
| Outdoor unit fan error |
| 1c |
Communication error (inverter to multi controller) |
| Communication error (inverter to multi controller) |
| 1d |
2 way valve sensor error |
| 2-way valve sensor error |
| 1E |
Expansion valve error |
| Expansion valve error |
| 1F |
Connection indoor unit error |
| |
Indoor unit connection error |
| GE |
E0 |
On 70 Pint models only - when water is not pumped out while the unit is running under the Pump mode, E0 and the pump light will flash on the display. |
| E1 |
Electronic control board function error. Unplug the window air conditioner for 1 minute and then plug it back in to reset the electronic control board. If the code doesn’t clear, unplug the window air conditioner and check the wire harness connections on the electronic control board. Check the electronic control board for visible damage such as a burn mark. Replace the electronic control board if it’s damaged or defective. |
| E4 |
Water bucket is full or defective bucket float switch. If the collection bucket is full, empty the bucket. If the bucket isn’t full, unplug the air conditioner and check the wire harness connections on the electronic control board. Check for a pinched or damaged wire in the wire harness between the electronic control board and the collection bucket float switch. Check the float switch for damage. If the float switch is defective, replace it. |
| 88 |
When power is connected to the unit, "88" will be displayed, this is normal. If a fault or error code appears on the display of the dehumidifier, disconnect power to the unit for 30 seconds. If the fault code reappears, review the Troubleshooting Tips in your Owner's Manual. |
| Gree |
E1 |
Refrigerant system high pressure protection |
| E2 |
Anti-freezing protection |
| E4 |
Compressor exhaust high temperature protection |
| E5 |
AC over-current protection |
| E6 |
Communication failure between indoor unit and outdoor unit |
| E8 |
Anti-high temperature protection |
| H6 |
No feedback of indoor fan motor |
| C5 |
Jumper cap malfunction protection |
| F0 |
Refrigerant Leakage Protection |
| F1 |
Indoor ambient sensor open or short circuit |
| F2 |
Indoor tube sensor open or short circuit |
| F3 |
Outdoor ambient sensor open or short circuit |
| F4 |
Outdoor tube sensor open or short circuit |
| F5 |
Exhaust sensor open or short circuit |
| F6 |
Over load limit / drop frequency |
| F8 |
Over current limit / drop frequency |
| F9 |
High exhaust temperature limit / drop frequency |
| PH |
Over voltage protection for PN |
| U5 |
AC current detect circuit malfunction |
| U4 |
Compressor reverse protection |
| P5 |
Over compressor phase current protection |
| b5 |
Inlet tube sensor malfunction |
| L3 |
Outdoor DC fan motor malfunction |
| b7 |
Outlet tube sensor malfunction |
| FC |
Door malfunction |
| FE |
Compressor overload sensor malfunction |
| H1 |
Defrosting |
| H2 |
Static clearing dust protection |
| H3 |
Compressor over load protection |
| H4 |
System abnormal protection |
| H5 |
IPM protection |
| HC |
PFC protection |
| H7 |
Compressor loss step protection |
| H0 |
Heating anti-high temperature drop frequency |
| Lc |
Startup failure |
| U2 |
Compressor protection against loss of phase |
| U1 |
Compressor phase current detection circuit malfunction |
| HE |
Compressor demagnetization protection |
| EE |
Loading EEPROM malfunction |
| P6 |
Communication failure between main board and driver board |
| PU |
Capacitor charge malfunction |
| P7 |
IPM sensor circuit malfunction |
| P8 |
IPM high temperature protection |
| U3 |
PN voltage drop protection |
| PL |
Low PN voltage protection |
| Pc |
Current detect circuit malfunction or Current sensor malfunction |
| Ld |
Compressor loss of phase protection |
| LE |
Compressor locked rotary protection |
| EU |
IPM over temperature limit / drop frequency |
| U7 |
4-way valve reversal abnormal |
| U8 |
Disconnection of the exhaust temperature sensor |
| U9 |
AC power zero voltage detect error |
| FA |
Over tube temperature drop frequency |
| FH |
Anti-freezing limit / drop frequency |
| oE |
PFC module temperature protection/PFC module sensor malfunction |
| Haier
|
E1 |
Indoor room temperature sensor failure |
| E2 |
Indoor coil temperature sensor failure |
| E4 |
EEPROM wrong |
| E7 |
Communication failure between indoor and outdoor |
| E14 |
Indoor fan motor failure |
| E18 |
Temperature cutoff protection |
| F1 |
Module failure |
| F2 |
Outdoor DC motor failure |
| F4 |
Compressor overheat / discharging temperature protection |
| F5 |
Module over current / current transducer failure |
| F6 |
Outdoor ambient temp. sensor abnormal |
| F7 |
Outdoor suction/defrosting temp. sensor abnormal |
| F8 |
High pressure abnormal |
| F9 |
Low pressure abnormal |
| F10 |
No AC power supply |
| F11 |
Outdoor PCB EEPROM abnormal |
| F13 |
Communication failure between outdoor PCB and module |
| F14 |
Compressor discharging temp. sensor failure |
| F15 |
Compressor running faulty |
| F16 |
Running state-detecting circuit failure |
| Hisense
|
00 |
No trouble |
| 01 |
Outdoor coil temperature sensor in trouble |
| 02 |
Compressor temperature sensor in trouble |
| 03 |
Voltage transformer in trouble |
| 04 |
Current transformer in trouble |
| 05 |
IPM module protection |
| 06 |
Over and under-voltage control |
| 07 |
Communication trouble |
| 08 |
Current overload control |
| 09 |
Maximum current control |
| 10 |
Communication trouble (between outdoor unit and driver unit) |
| 11 |
Outdoor EEPROM in trouble |
| 13 |
Compressor exhaust temperature too high control |
| 14 |
Outdoor ambient temperature sensor in trouble |
| 15 |
Compressor housing temperature control |
| 16 |
Anti-freeze or overload control |
| 18 |
DC compressor fails to start |
| 19 |
DC compressor out of step |
| 33 |
Room temperature sensor in trouble |
| 34 |
Indoor coil temperature sensor in trouble |
| 35 |
Between wire remote controller and indoor unit communication trouble |
| 36 |
Communication between the indoor and outdoor in trouble |
| 37 |
Water overbrimmed the pump |
| 38 |
Indoor EEPROM in trouble |
| 39 |
Indoor fan motor operation abnormal |
| 40 |
Grid protection alarm (cabinet type) |
| 41 |
Detecting failures by zero-crossing |
| F0 | Wire remote controller EEPROM failure. Change wire remote controller. |
| F1 |
Wire remote controller temperature sensor failure. Change wire remote controller. |
| F2 |
Wire remote controller clock IC failure. Change wire remote controller. |
| F3 |
Wire remote controller humidity sensor failure. Change wire remote controller. |
| FE |
Communication between main control board & Wiring remote controller Fault (display on wiring remote controller). |
| ER |
Communication between main control board &display board Fault. |
| Hitachi |
P01 |
Pressure ratio protection control |
| P02 |
High pressure increase protection |
| P03 |
Inverter current protection |
| P04 |
Inverter fin temperature increase protection |
| P05 |
Discharge gas temperature increase protection at the upper part of the compressor |
| P06 |
Low pressure decrease protection |
| P09 |
High pressure decrease protection |
| P0A |
Demand current protection control |
| P0d |
Low pressure increase protection |
| P11 |
Pressure ratio decrease retry |
| P12 |
Low pressure increase retry |
| P13 |
High pressure increase retry |
| P14 |
Constant speed compressor overcurrent retry |
| P15 |
Discharge gas temperature increase retry / Low pressure decrease retry |
| P16 |
Discharge gas super-heat decrease retry |
| P17 |
Inverter anomaly retry |
| P18 |
Abnormal Inverter voltage retry / Inverter failure retry |
| P26 |
High pressure decrease retry |
| LG |
C1 or CH1 |
Indoor temperature sensor open or closed circuit. |
| C2 or CH2 |
Outdoor temperature sensor open or closed circuit. |
| C4 or CH4 |
Heat sink temperature sensor open or closed circuit. |
| C5 or CH5 |
Communication between indoor and outdoor units. |
| C6 or CH6 |
Excessive current at inverter DC power circuit. |
| C7 or CH7 |
Excessive compressor current |
| C8 or CH8 |
Indoor fan not rotating. |
| C9 or CH9 |
Outdoor fan not rotating. |
| CA |
1. Discharge temp more than130 °C 2. Faulty discharge thermistor |
| CC |
EEPROM error |
| CD |
Inverter module error |
| Po |
System in Power Mode – not a fault |
| Lo |
System in test mode – not a fault |
| Samsung |
E101 |
Communication Error (Indoor Outdoor) |
| E102 |
Communication Error (Indoor Outdoor) |
| E121 |
ROOM TH sensor error |
| E122 |
INDOOR MID, INDOOR IN PIPE-TH sensor error |
| E154 |
Fan Error (Indoor) |
| E162 |
EEPROM Error (Indoor) |
| E163 |
Option Error |
| E203 |
Time out Comm. (Inv Micom Main Micom) |
| E221 |
OUT-TH(Outdoor Temperature) Sensor Error |
| E231 |
CON-TH(Cond Temperature) Sensor Error |
| E251 |
DIS-TH(Discharge Temperature) Sensor Error |
| E416 |
DIS-TH(Discharge Temperature) Over Error |
| E422 |
EEV or Valve Close error-Self diagnosis |
| E440 |
Prohibit Operation Condition Error (Heating) |
| E441 |
Prohibit Operation Condition Error (Cooling) |
| E458 |
Fan Error(Outdoor) |
| E461 |
Comp Starting Error |
| E462 |
AC Input I_Limit Trip Error |
| E464 |
IPM Over Current(O.C) Error |
| E465 |
Comp V_limit/I_limit Error |
| E466 |
DC-Link Voltage Under/Over Error |
| E467 |
Comp Wire Missing Error |
| E468 |
Current Sensor Error |
| E469 |
DC-Link Voltage Sensor Error |
| E470 |
EEPROM Data Error (no data) |
| E471 |
EEPROM Data Error (Main Micom Inv Micom) |
| E474 |
Heatsink Sensor Error |
| E483 |
Over Voltage Protection Error |
| E484 |
PFC Over Load Error |
| E485 |
Input Current Sensor Error |
| E488 |
AC Input Voltage Sensor Error |
| E500 |
Heatsink Over Temperature Error |
| E554 |
Gas Leak Error |
| Sharp |
EE |
Buttons are locked |
| E0 |
Water pump malffunction |
| E1 |
High pressure protection of compressor |
| E2 |
Indoor anti-frozen of compressor |
| E3 |
Low pressure protection of compressor |
| E4 |
Air discharge high-temperature protection of compressor |
| E5 |
Overload protection of compressor |
| E6 |
Transmit malfunction |
| E8 |
Indoor fan protection |
| E9 |
Water flow protection |
| FF |
Connected control communications Failure |
| F0 |
Malfunction of indoor environment sensor at air return vent |
| F1 |
Evaporator sensor malfunction |
| F2 |
Condenser sensor malfunction |
| F3 |
Outdoor environment sensor malfunction |
| F4 |
Malfunction of air discharge sensor |
| F5 |
Malfunction of environment sensor on displayer |
| ee |
Malfunction of outdoor drive memory chip. Outdoor drive board. |
| H3 |
Compressor over load protection. Compressor overload switch. |
| H4 |
Overload protection. Evaporator temperature, condenser temperature. |
| H6 |
Malfunction of outdoor fan motor. Outdoor fan motor. |
| U7 |
Direction changing malfunction of 4-way valve. |
| P6 |
Communicatio n malfunction between main control and drive. |
| EE |
Malfunction of outdoor main control memory chip. Outdoor main control board. |
| TCL |
E0 |
Indoor/outdoor communication fault |
| EC |
Outdoor communication fault |
| E1 |
Room temperature sensor (IRT) |
| E2 |
Indoor pipe (coil) temperature sensor (IPT) |
| E3 |
Outdoor pipe (coil) temperature sensor (OPT) |
| E4 |
System abnormal |
| E5 |
Model configuration wrong |
| E6 |
Indoor fan motor fault |
| E7 |
Outdoor temperature sensor |
| E8 |
Exhaust temperature sensor |
| E9 |
Intelligent power module of drive and module fault |
| EF |
Outdoor fan motor fault (DC Motor) |
| EA |
Current sensor fault |
| EE |
EEPROM fault |
| EP |
Temperature switch fault (on top of the compressor) |
| EU |
Voltage sensor fault |
| EH |
Intake temperature sensor |
| P1 |
Overvoltage / undervoltage protection |
| P2 |
Overcurrent protection |
| P4 |
Exhaust overtemperature protection |
| P5 |
Subcooling protection under cooling mode |
| P6 |
Overheating protection under cooling mode |
| P7 |
Overheating protection under heating mode |
| P8 |
Outdoor overtemperature / undertemperature protection |
| P9 |
Drive protection (software control ) |
| P0 |
Module protection (hardware control) |
| Toshiba |
E01 |
No communication between remote controller and indoor unit. |
| E02 |
Local controller failure - unable to transmit |
| E03 |
Master indoor unit receives no data to A-B |
| E04 |
Indoor unit (except twin slave) receives no communications from outdoor unit; can also include klixon on discharge pipe of outdoor unit |
| E08 |
Duplicated indoor unit address |
| E09 |
2 local controllers connected on a group - both configured as masters |
| E10 |
Indoor unit PSB failure |
| E18 |
Communications failure between master indoor unit and slave indoor unit or units |
| F01 |
Indoor unit TCJ (Liquid) sensor error (Open or Closed circuit - resistance is measured in kΩ |
| F02 |
Indoor unit TC2 (Vapour) sesnor error (Open or Closed circuit - resistance is measured in kΩ |
| F04 |
Outdoor unit TD (Discharge) sesnor error (Open or Closed circuit - resistance is measured in kΩ |
| F06 |
Outdoor unit TE (Coil) sesnor error (Open or Closed circuit - resistance is emasured in kΩ |
| F08 |
Outdoor unit TO (Ambient) sesnor error (Open or Closed circuit - resistance is measured in kΩ |
| F10 |
Indoor unit TA (Return Air) sesnor error )Open or Closed circuit - resistance is measure in kΩ |
| F29 |
Indoor unit PCB failure |
| H01 |
Outdoor unit inverter compressor over current detected |
| H02 |
Master outdoor unit over current detected shortly after start up |
| H03 |
Current detected on Master outdoor unit whilst idle |
| H06 |
Outdoor unit Low pressure detected by Ps sensor (0.2 bar -n 2.9 psig) |
| L03 |
Indoor unit Duplicated master indoor units in a group |
| L07 |
Indoor unit in a group of units previously addressed as a single unit - check addressing |
| L08 |
Indoor units addresses not set - check addressing |
| L09 |
Indoor units capacity not set (check DN Code 11) |
| L29 |
Outdoor unit IPDU error (Number of detected IPDU units is reduced) |
| L30 |
Input on indoor PCB CN80 circuit for 1 minute |
| L31 |
Outdoor unit PCB error |
| P01 |
Indoor unit fan motor error |
| P03 |
Outdoor unit High discharge temperature (TD1 exceeded 115°C) |
| P04 |
Outdoor unit High pressure switch activated (Detected by high temperature on TE sensor on digital/super digital inverter units) |
| P07 |
Outdoor unit PCB heat sink overheated (Temperature over 90°C recorded) |
| P10 |
Indoor unit Float switch activated |
| P12 |
Indoor unit fan motor error - detected by feedback circuit |
| P19 |
Wrong change in temperature recorded (4 way valve error) |
| P22 |
Outdoor unit fan motor IPDU error |
| P26 |
Outdoor unit Giant transistor short circuit |
| P29 |
Outdoor unit Compressor error detected by feedback circuit |
| P30 |
Indoor unit Group control follower unit error / duplicated central control addresses |
| P31 |
Indoor unit PCB error |
| C05 |
Central control Sending error in TCC-Link central control device |
| C06 |
Central control Receive error in TCC-Link central control device |
| C12 |
Batch alarm for general purpose equipment interface |
| Westinghouse
|
E0 |
Indoor unit EEPROM parameter error. |
| E1 |
Indoor / outdoor units communication error. |
| E2 |
Zero-crossing signal detection error. |
| E3 |
Indoor fan speed has been out of control. |
| E4 |
Open circuit or short circuit of indoor room temperature T1 sensor. |
| E5 |
Open circuit or short circuit of evaporator coil temperature T2 sensor |
| EC |
Refrigerant Leakage Detection |
| F1 |
Open circuit or short circuit of outdoor ambient T4 temperature sensor |
| F2 |
Open circuit or short circuit of condenser coil temperature T3 sensor |
| F3 |
Open circuit or short circuit of compressor discharge T5 temperature sensor |
| F4 |
Outdoor unit EEPROM parameter error |
| P0 |
IPM malfunction or IGBT over-strong current protection |
| P1 |
Over voltage or over low voltage protection |
| P2 |
High temperature protection of compressor top diagnosis and solution |
| P4 |